Customization: | Available |
---|---|
Theory: | Electromagnetic Relay |
Usage: | Household Appliances Relay, Communication Relay |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | Overvoltage monitoring | Undervoltage monitoring | Asymmetry protection | Phase sequence protection | Phase failure protection | Selectable function | |||||
setting range | time-delay | setting range | time-delay | setting range | time-delay | ||||||
ZHRV1-01 | 1.05-1.30 | 0.1-10s | N | N | N | N | N | Y | manual reset and test button | PTC protection | L1/L2/L3 load side protection |
ZHRV1-02 | N | N | 0.70-0.95 | 0.1-10s | N | N | N | Y | |||
ZHRV1-03 | 1.05-1.30 | 0.1-10s | 0.70-0.95 | 0.1-10s | N | N | N | Y | manual reset button | ||
ZHRV1-04 | 1.05-1.30 | 0.1-10s | 0.70-0.95 | 0.1-10s | N | N | Y | Y | |||
ZHRV1-05 | 1.05-1.30 | 0.1-10s | 0.70-0.95 | 0.1-10s | 8% | 2s | N | Y | |||
ZHRV1-06 | 1.05-1.30 | 0.1-10s | 0.70-0.95 | 0.1-10s | 8% | 2s | Y | Y | |||
ZHRV1-07 | 1.05-1.30 | 0.1-10s | 0.70-0.95 | 0.1-10s | 5%-15% | 0.1-10s | N | Y | N | ||
ZHRV1-08 | 1.05-1.30 | 0.1-10s | 0.70-0.95 | 0.1-10s | 5%-15% | 0.1-10s | Y | Y | |||
ZHRV1-09 | 1.05-1.30 | 2s | 0.70-0.96 | 2s | 8% | 2s | N | Y | manual reset and test button | ||
ZHRV1-10 | 1.15 | 2s | 0.85 | 2s | 8% | 2s | Y | Y | |||
ZHRV1-11 | 1.15 | 2s | 0.85 | 2s | 5%-15% | 0.1-10s | N | Y | |||
ZHRV1-12 | 1.15 | 2s | 0.85 | 2s | 5%-15% | 0.1-10s | Y | Y | |||
ZHRV1-13 | 1.15 | 2s | 0.85 | 2s | 8% | 2s | N | Y | |||
ZHRV1-14 | 1.15 | 2s | 0.85 | 2s | 8% | 2s | Y | Y | |||
ZHRV1-15 | 1.15 | 2s | 0.85 | 2s | N | N | N | Y | |||
ZHRV1-16 | 1.15 | 2s | 0.85 | 2s | N | N | Y | Y | |||
ZHRV1-17 | N | N | N | N | 5%-15% | 0.1-10s | Y | Y | |||
ZHRV1-18 | N | N | N | N | N | N | Y | Y | |||
ZHRV1-19 | N | N | N | N | 8% | 2s | Y | Y | |||
Note: 1. Y the function is available, N the function is not available | |||||||||||
2. In the circuit of three phase four wire, the relay which have no phase sequence protection function can be used to protect single phase or two phase circuit. | |||||||||||
3. For PTC temperature protection functionand load side protection function, only one kind of function can be shosen. Load side protection function is only available for the circuit of three phases four wires. | |||||||||||
4. All models relay can be adjusted in 220V/230V/240V or 380V/400V/415V except RV1 -07, RV1 -08 |
Rated supply voltage | AC220V,AC230,AC240V,AC380V,AC400V,AC415V |
Rated supply frequency | 50Hz/60Hz |
Over-voltage threshold range | (1.05~1.30)*Ue |
Under-voltage threshold range | (0.70~0.95)*Ue |
Unbalance threshold range | 5%-15% |
Action delay range | 0.1s-10s |
Phase failure and phase sequence | ≤1s |
Voltage measurement error | ≤1%(Entire setting range) |
Delay error | ±10%+0.1s |
Knob setting accuracy | ±1% scale value |
Rated insulation voltage | 415V |
Contact configuration capacity(A) | 10A |
IP Class | IP20 |
Class of pollution | 3 |
Electrical life | 105 |
Mechanicall life | 106 |
Altitude | ≤2000m |
Allowable relative humidity | ≤50%(40ºC)(no condensation) |
Use category | AC-15 |
Short circuit protector type | RT36-00 5A |
Contact capacity | Ue/le:240V/1.5A,415V/0.95A |
Output type | 1C/O |
DIN rail standard | width 35mm(IEC/EN60715) |