Customization: | Available |
---|---|
Theory: | Electromagnetic Relay |
Usage: | Household Appliances Relay, Air Conditioning Units,Elevator Machine Room,Pumps |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated supply voltage | (3-phase 3-wire) 220V~450V AC |
Rated supply frequency | 50Hz/60Hz |
Phase failure and phase sequence | ≤0.5s |
Delay error | ±10%+0.1s |
Measurement accuracy | 1%, RMS |
Data storage time | 10years |
Maximum counting capacity | 999999 |
Maximum timing capacity | 9999h59m |
Maximum count frequency | 50Hz |
Accumulated timing error | ≤1.001% |
Count input signal | AC/DC 20V-450V |
Contact configuration capacity(A) | 10A |
IP Class | IP20 |
Class of pollution | 3 |
Electrical Life | 105 |
Mechanical life | 106 |
Altitude | ≤2000m |
Allowable relative humidity | ≤50%(40ºC)(No condensation) |
Use category | AC-15 |
Short circuit protector type and maximum rating | NT00-6A |
Contact capacity | Ue/le:240V/1.5A,415V/0.95A |
Output type | 1C/O+1NC |
DIN rail Standard | width 35mm(IEC/EN60715) |
Type | code | Technical parameter | Setting range | Factory setting | Step amount |
Voltage setting |
F11 | Over-voltage action value | OFF-381V~500V | 437V | 1V |
F12 | Under-voltage action value | 260V~379V-OFF | 304V | 1V | |
F13 | Over-voltage/Under-voltage hysteresis | 1~20V | 5V | 1V | |
F14 | Unbalance action value | OFF-20V~80V | 32 | 1V | |
Time setting |
F15 | Unbalance hysteresis | 3V~15~ | 5V | 1V |
FF21 | Over-voltage delay | 0.1~20S | 2s | 0.1S | |
F22 | Under-voltage delay | 0.1~20S | 5s | 0.1S | |
F23 | Unbalance delay | 0.1~20S | 2s | 0.1S | |
F24 | delay | 0.3~30S | 2s | 0.1S | |
F25 | Reset delay | 0.3~30S | 2s | 0.1S | |
Protection Setting |
F31 | Phase sequence protection | ON-OFF | ON | / |
F32 | Self-reset function | ON | ON | / | |
Function setting | F90 | Restore factory setting | ON | OFF | / |
F91 | Timing & counting cleared | ON | OFF | / | |
End | Exit setup |