| Rated supply voltage | M415(3-phase 3-wire)AC200V~500V M240(3-phase 4-wire)AC125V~300V |
| Rated supply frequency | 50Hz/60Hz |
| Voltage measurement error | ≤1% (Entire setting range) |
| Delay error | ±10%+0.1s |
| Measurement accuracy | 1%, RMS |
| Phase failure and phase sequence | ≤0.2s |
| Rated insulation voltage | 415V |
| Contact configuration capacity(A) | 10A |
| IP Class | IP20 |
| Class of pollution | 3 |
| Electrical Life | 105 |
| Mechanical life | 106 |
| Altitude | ≤2000m |
| Allowable relative humidity | ≤50%(40ºC)(No condensation) |
| Use category | AC-15 |
| Short circuit protector type | RT36-00 5A |
| Contact capacity | Ue/le:240V/1.5A,415V/0.95A |
| Output type | 1C/O |
| DIN rail Standard | Width 35mm(IEC/EN60715) |
| Parameters | Setting range | Step amount | Factory setting | Remarks |
| Over-voltage action value | OFF-381V~500V | 1V | 437V | M415 |
| OFF-221V~300V | 1V | 253V | M240 | |
| Over-voltage delay | 0.1~20S | 0.1s | 2s | |
| Under-voltage action value | 260V~379V-OFF | 1V | 323V | M415 |
| 150V~219V-OFF | 1V | 187V | M240 | |
| Under-voltage delay | 0.1~20s | 0.1s | 2s | |
| Unbalance rate | OFF-5%~20% | 1% | 8% | |
| Asymmetry Delay time | 0.1~20s | 0.1s | 2s | |
| Phase sequence protection | ON-OFF | ON | ||
| Start/reset delay | 0.3~30S | 0.1s | 0.3s | |
| Automatic reset | ON-OFF | ON |