ZHRV series Electromechnical Motor Protective Relay and Three phase AC Voltage monitoring Relay and Protector
Feature:
1, Microprocessor base
2, True RMS measurement, measuring accuracy≤ 1%
3, Can be Used for monitoring circuit of single phase, two phase,
Three phase three wire or three phase four wire
4, LED indication for control state
5, 36mm width
Application:
1, Protection electromechnical device against voltage faults
2, Protection against a driving load (phase failure)
3, Normal/emergency power supply switching
4, Protection electromechnical device against reverse running
Working range:
Factory control system, power compensation system, switchboard, air-conditioning system, motor controlling.
Functions:
Overvoltage monitoring, Undervoltage monitoring. Phase failure monitoring
Model |
Overvoltage monitoring |
Undervoltage monitoring |
Asymmetry protection |
Phase sequence protection |
Phase failure protection |
setting range |
time-delay range |
setting range |
time-delay range |
setting range |
time-delay range |
ZHRV2-01 |
N |
N |
N |
N |
N |
N |
Y |
Y |
ZHRV2-02 |
N |
N |
N |
N |
8% |
2s |
Y |
Y |
ZHRV2-03 |
1.05-1.30 |
0.1-10s |
0.70-0.95 |
0.1-10s |
N |
N |
N |
Y |
ZHRV2-04 |
1.05-1.30 |
0.1-10s |
0.70-0.95 |
0.1-10s |
N |
N |
Y |
Y |
ZHRV2-05 |
1.15 |
2s |
0.85 |
2s |
N |
N |
Y |
Y |
ZHRV2-06 |
N |
N |
N |
N |
5%-15% |
0.1-10s |
Y |
Y |
ZHRV2-07 |
1.05-1.30 |
0.1-10s |
0.70-0.95 |
0.1-10s |
5%-15% |
0.1-10s |
N |
Y |
ZHRV2-08 |
1.05-1.30 |
0.1-10s |
0.70-0.95 |
0.1-10s |
5%-15% |
0.1-10s |
Y |
Y |
ZHRV2-09 |
1.15 |
2s |
0.85 |
2s |
8% |
2s |
N |
Y |
ZHRV2-10 |
1.15 |
2s |
0.85 |
2s |
8% |
2s |
Y |
Y |
ZHRV2-11 |
1.15 |
2s |
0.85 |
2s |
8% |
3s |
Y |
Y |
Note: 1. Y the function is available, N the function is not available |
2. In the circuit of three phase four wire, the relay which have no phase sequence protection function can be used to protect single phase or two phase circuit. |
3. All models relay can be adjusted in 220V/230V/240V or 380V/400V/415V except RV2 -07, RV2 -08 |
Description of panel diagram:
I. Function indicator lamp:
a. Power indicator lamp: indication of power supply for relay
b. Normal: no fault of relay indicated
c. Operation: output relay operation indication
d. Over-voltage: over-voltage fault indication
e. Under-voltage: under-voltage fault indication
f. Phase dislocation: indication of input phase sequence errors
g. Phase failure: indication of phase failure fault
h. Unbalance: three-phase imbalance fault indication
i. Over-voltage/under-voltage: in case of over-voltage fault, the indicator lamp would be constantly ON; in case of under-voltage,
the fault indicator lamp would flash.
j. Over-voltage/under-voltage/recovery: when overvoltage fault occurs, the indicator lamp would flash at a high frequency (flash once every
0.3s); in case of under-voltage fault, the indicator lamp would flash at a low frequency (once every 1.5s); in case of recovery delay, the indicator lamp would be constantly ON.
II. Setting knob:
a. ×Ue: knob for setting of threshold values of over-voltage (1.05~1.30) or under-voltage (0.70~0.95)
b. T(s): operation time delay adjusting knob 0.1s~10s
c. Over_t(s): over-voltage operation time delay adjusting knob 0.1s~10s
d. Under_t(s): under-voltage operation time delay adjusting knob 0.1s~10s
e. Asm (%): knob for setting of threshold value of unbalance 5%~15% Over-voltage threshold value = set value × Ue,Under-voltage threshold value = set value × Ue
Wiring diagram of a threephase three-wire system Wiring diagram of a threephase four-wire system
Wiring diagram of singlephase and two-phase system Wiring diagram of a threephase three-wire system
(load end protection)
Q1.Are you a factory or trading company ?
A:We are a factory founded in 2010 and have over 10 years'OEM and international trading experience .
Q2.What's your main product?
A:Our main products are time Relay, voltage Relay, motor protector, current relay,solid state relay
Q3.Do you accept OEM or ODM?
A:Of course.
Q4.What's your main payment term?
A:T/T ,LC ,D/P.
Q5.Any quality guarantee or after-sales service?
A:All the products have 2 years' Guarantee. If any quality complaint , we will give out solution within 5 days
Q6.Can sample fee be returned back to me ?
A:Sample amount can be deducted from your bulk order payment when order quantity is over 1000 pieces at the first time.