ZHRV series Electromechnical Motor Protective Relay
Applications:
Protection electromechnical device against voltage faults. Protection electromechnical device against reverse running. Protection against a driving load (phase failure) Normal/emergency power supply switching.
Functions:
Overvoltage monitoring, Undervoltage monitoring, Phase sequence monitoring, Phase failure monitoring, Asymmetry monitoring, PTC protection
Technical parameters:
Features:
Microprocessor base.
Modular design, 36mm width
True RMS measurement, measuring accuracy&less; 1%.
Wide frequency range(45-65Hz) measurement
8 nominal operating voltage selectable
Reset delay adjustable
LED indication for control state
Communication through Modbus module
Rated supply voltage: P-P: AC 3× 208--3× 440V; P-N: AC 3× 120--3× 254V
Rated operating voltage range: P-P: AC 166V--528V; P-N: AC 96V--329V
Voltage measuring range: AC 166V--528V; AC 96V--329V
Model |
Overvoltage |
Undervoltage |
Asymmetry |
Trip delay |
Phase sequence |
Phase failure |
Operating voltage |
Reset time |
Output Contact |
Rated operating |
Selectable |
voltage(Un) |
ZHRV3-01 |
- |
- |
- |
0.1~10s |
√ |
√ |
√ |
0.1~10s |
Z: 2 C/O, M: Mobus+1 C/O |
A440: AC(3phase 3wire) 208V, 220V 230V, 240V 380V, 400V 415V, 440V AN254: AC(3phase 4wire) 120V, 127V 132V 138V 220V, 230V 240V, 254V |
ZHRV3-02 |
2%~20% |
- |
5%~15% |
0.1~10s |
√ |
√ |
√ |
0.1~10s |
ZHRV3-03 |
- |
- |
- |
0.1~10s |
- |
√ |
√ |
0.1~10s |
ZHRV3-04 |
2%~20% |
2%~20% |
- |
0.1~10s |
- |
√ |
√ |
0.1~10s |
Z: 2C/O, C: 1C/O+1C/O, Mobus+1C/O |
ZHRV3-05 |
2%~20% |
2%~20% |
- |
0.1~10s |
- |
√ |
√ |
0.1~10s |
Z: 2C/O, M: Mobus+1C/O |
ZHRV3-06 |
2%~20% |
2%~20% |
5%~15% |
0.1~10s |
√ |
√ |
√ |
0.1~10s |
ZHRV3-07 |
2%~20% |
2%~20% |
5%~15% |
0.1~10s |
√ |
√ |
√ |
0.1~10s |
ZHRV3-08 |
15% |
2%~20% |
|
2s |
√ |
√ |
√ |
2s |
ZHRV3-09 |
15% |
- |
|
2s |
√ |
√ |
√ |
2s |
ZHRV3-10 |
15% |
15% |
8% |
2s |
√ |
√ |
√ |
2s |
ZHRV3-11 |
15% |
15% |
8% |
2s |
√ |
√ |
√ |
2s |
Description of Function diagram and LED
Operating Instructions
1. Set the rated voltage range control knob.
The position of this knob is only taken into account on energisation of the device.If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the vol tage selected at the time of energisation preceding the change of position.
The LED's return to their normal state if the switch is returned to the origin al position selected prior to the last energisation.
2.After the relay is powered on, the output relay would not close until the reset delay time elapses.
3. In case of voltage failure, the relay would be disconnected at the expiration of set time delay interval.
4. If the relay detects voltage failure during electrification, the output re lay would be kept in off-state.
5. The measured voltage U<Un*70% indicates open phase fault.
6. In 3 phase 3 wires system(M440) phase fault at power input terminals L1 and L3, the function LED would not make indication.
In 3 phase 4 wires system(M254) phase fault at power input terminals L1 and L3, the function LED would not make indication.
Overall Dimensions
Wiring Diagram
More Products
Q1.Are you a factory or trading company ?
A:We are a factory founded in 2010 and have over 10 years'OEM and international trading experience .
Q2.What's your main product?
A:Our main products are time Relay, voltage Relay, motor protector, current relay,solid state relay
Q3.Do you accept OEM or ODM?
A:Of course.
Q4.What's your main payment term?
A:T/T ,LC ,D/P.
Q5.Any quality guarantee or after-sales service?
A:All the products have 2 years' Guarantee. If any quality complaint , we will give out solution within 5 days
Q6.Can sample fee be returned back to me ?
A:Sample amount can be deducted from your bulk order payment when order quantity is over 1000 pieces at the first time.